3516B (50 Hz) Generator Set

Bore
6.69 in
Displacement (HD)
4764.73 in3
Stroke (HD)
8.46 in
Aspiration
TA

Engine Specifications

Bore
6.69in
Displacement (HD)
4764.73in3
Stroke (HD)
8.46in
Aspiration
TA
Fuel System
Electronic unit injection
Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Displacement - Std
4210.64in³
Stroke - Standard
7.48in
Compression Ratio
15.5:1
Governor Type
Ademâ„¢3
Stroke
8.46in
Displacement
4764.73in
Aspiration
TA
Fuel System
Electronic unit injection
Bore
6.69in
Displacement - HD
4764.73in³
Stroke - HD

Generator Set Dimensions

Length - Maximum
251.7in
Width - Maximum
90in
Height - Maximum
93.2in
Dry Weight - Genset (maximum)
40320lb
Length - Minimum
233.4in
Dry Weight - Genset (minimum)
31900lb

Generator Set Specifications

Standby Rating
2500 kVA
Prime Power Rating
2275 kVA
Minimum Rating
2000 kVA
Maximum Rating
2500 kVA
Voltage
380 to 11000 Volts
Frequency
50 Hz
Speed
1500 rpm
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Standard Equipment:

  • Air Inlet
    • Air cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Secondary fuel filters
    • Fuel priming pump
    • Primary fuel filter with integral water separator
  • Generator
    • Matched to the performance and output characteristics of Cat engines
    • IP23 Protection
  • Power Termination
    • Busbar
  • Control Panel
    • EMCP 4.2B
  • General
    • Paint - Caterpillar yellow except rails and radiators gloss black

Optional Equipment:

  • Exhaust
    • Exhaust mufflers (except Tier 4)
  • Generator
    • Permanent magnet excitation (PMG)
    • Internal excitation (IE)
    • Anti-condensation heater
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • Generator temperature monitoring & protection
    • Digital I/O module
    • Load share module
    • EMCP 4.3, EMCP 4.4
    • Remote monitoring software
  • Mounting
    • Spring type vibration isolators
    • IBC isolators
    • Rubber anti-vibration mounts
  • Starting/charging
    • Oversize batteries
    • Charging alternator
    • Heavy duty starting system
    • Jacket water heater
    • Air starting motor with control and silencer
    • Battery chargers
  • General
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • EU Certificate of Conformance (CE)
    • The following options are based on regional and product configuration:
    • Enclosures: Sound attenuated, weather protective
    • Automatic transfer switches (ATS)
    • UL 2200 package
    • Integral & sub-base UL listed dual wall fuel tanks
    • Integral & sub-base fuel tanks
    • EEC Declaration of Conformity
    • CSA Certification