C4.4 Generator Set

Bore
4.13 in
Displacement
268.5 in
Stroke
5 in
Fuel System
Electronic (adjustable)

Engine Specifications

Bore
4.13in
Displacement
268.5in
Stroke
5in
Fuel System
Electronic (adjustable)
Aspiration
Turbocharged
Engine Model
C4.4, In-line 4, 4-cycle diesel
Compression Ratio
18.2:1
Governor Type
Adem™A4
Fuel System
Electronic (adjustable)
Bore
4.13in
Displacement
268.5in
Stroke
5in

Generator Set Specifications

Duty Cycle
Standby, Prime
Minimum Rating
36 ekW
Maximum Rating
100 ekW
Voltage
220 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Emissions/Fuel Strategy
Non Regulated, EU Stage II

Generator Set Dimensions

Height - Maximum
53.6in
Length - Maximum
75.8in
Width - Maximum
44.1in

Standard Equipment:

  • Air Inlet System
    • Air cleaner; light duty with disposable element
  • Air Inlet
    • Air Cleaner
  • Cooling
    • Package mounted radiator
  • Cooling System
    • Fan drive, battery charging alternator drive
    • Radiator and cooling fan with guards
    • Coolant drain line with valve
    • Caterpillar extended life coolant
  • Exhaust
    • Exhaust flange outlet
  • Control Panel
    • EMCP 4.1
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Standard open set fuel tank / base supplied base, formed steel with single wall integral 8-hour fuel tank
  • Fuel
    • Secondary fuel filter
    • Primary fuel filter with integral water separator
    • Fuel priming pump
  • Generator
    • Segregated low voltage (AC/DC) wiring panel
    • Voltage regulator (single phase sensing)
    • Matched to the performance and output characteristics of Cat engines
    • 12 Leads
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Tower panel, IP22, bottom cable entry
    • IP23 protection
  • Governing System
    • Mechanical and electrical governing system - model dependent
  • Lube System
    • Lubricating oil
    • Oil drain line with valve
  • Power Termination
    • Bus Bar
  • Mounting System
    • Captive linear vibration isolators between base and engine-generator
    • Includes lifting provision and drag points
    • Termination points for coolant and lube oil drain lines
  • Mounting
    • Rubber vibration isolators
  • Starting/charging System
    • 24V battery with rack and cables
  • General
    • Paint - Caterpillar Yellow except rails and radiators gloss black
    • Engine and alternator pre-paint, Caterpillar yellow
  • Starting/charging
    • 24 volt starting motor
    • Batteries

Optional Equipment:

  • Exhaust
    • Industrial, Residential, Critical Mufflers
  • Generator
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Oversize and premium generators
    • Anti-condensation heater
  • Alternator System
    • 3 phase sensing
    • Permanent magnet
    • R frame auxilliary winding
    • Quadrature droop kit
    • LC frame alternator with coastal insulation protection
  • Circuit Breakers
    • Circuit Breaker Upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
  • Power Termination
    • Circuit breakers, IEC compliant
    • Circuit breakers, UL listed
  • Control Panels
    • EMCP (4.2) (4.3) (4.4)
    • Load share module
    • Digital I/O module
    • Remote monitoring software
    • Local & remote annunciator modules
  • Cooling System
    • Coolant heater
    • Low coolant level shutdown
    • Low coolant temp alarm
  • Control Panel Options
    • Earth fault (2 wire only)
    • EMCP 4.2
    • Volt free contacts
    • Emergency stop with key
    • Battery charger
    • Panel mounted audible alarm
    • Control panel heater
    • Speed adjust potentiometer
    • Voltage adjust potentiometer
    • Earth leakage (2 wire only)
    • Overload shutdown via breaker
  • Starting/charging
    • Jacket water heater
    • Charging alternator
    • Heavy-duty starting system
    • Battery chargers
    • Oversize batteries
  • Enclosures
    • Sound attenuated Level 2 enclosure
    • Sound attenuated Level 1 (galv)
    • Rental pack - CAE rental option only
  • European Certifications
    • Upgrade to STD set for CE
  • Fuel System
    • Compact skidbase for open set
    • Low fuel level alarm
    • Low fuel level shutdown
    • Bunded fuel tank
    • Open set narrow base
    • Skidbase for CALG enclosure sets
    • High fuel level alarm
  • General
    • Single or dual wall sub-base fuel tanks
    • EU Certificate of Conformance (CE)
    • CSA Certification
    • Single or dual wall integral fuel tanks
    • Automatic transfer switches (ATS)
    • Narrow, Wide or Skid Base
    • UL 2200 package
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • EEC Declaration of Conformity
    • Integral & sub-base fuel tanks
  • Global Certifications
    • Certification for CIS
  • Mounting Options
    • Battery removal
    • Electronic governor
    • Industrial silencer
    • Silencer installation kit
    • External single point lift - enclosure
  • Special Packing/inspectons For Shipment
    • PGS test report @ 1.0 power factor
    • PGS test report @ 0.8 power factor
  • General - Accessories / Miscellaneous
    • Packing case - compact set
    • Stone guards / rad trans flange
    • Packing case - canopied set