Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Maximum Rating 132 ekW
Minimum Rating 132 ekW
Emissions/Fuel Strategy Non Regulated
Voltage 220 to 480 Volts
Duty Cycle Standby
Emissions/Fuel Strategy Non Regulated
Frequency 60 Hz
Maximum Rating 132 ekW
Minimum Rating 132 ekW
Speed 1800 rpm
Voltage 220 to 480 Volts
Aspiration Turbocharged
Bore 4.1in
Compression Ratio 18.2:1
Displacement 427.8in³
Engine Model C7.1 I-6, 4-Cycle Diesel
Fuel System Inline
Governor Type Mechanical
Stroke 5.3in
Dry Weight - Genset (maximum) 4043lb
Height - Maximum 65.6in
Length - Maximum 130.9in
Width - Maximum 44.6in
C7.1, Inline 6 cylinder, 4 stroke diesel
GCCP 1.1
Single wall 8 hour fuel tank
Mechanical governor
Cat GC enclosure
A Frame standard alternator
Enclosure silencer
Engine and alternator pre-paint, Caterpillar yellow
120V
Certificate of Conformance
Australia, CIS, Gulf Certification
Space heater
Dual wall 8 hour fuel tank
Low fuel level alarm
High fuel level alarm
Low fuel level shutdown
Single wall tank with containment
3 Pole Circuit breaker 630A
4 Pole Circuit breaker 250A
4 Pole Circuit breaker 200A
3 Pole Circuit breaker 250A
3 Pole Circuit breaker 200A
4 Pole Circuit breaker 400A
4 Pole Circuit breaker 630A
Circuit breaker padlock
Neutral earth link
Overload via alarm switch on breaker
3 Pole Circuit breaker 400A
Panel mounted audible alarm
Battery charger
Earth leakage
Volt free contacts for genset running
Volt free contacts for common alarm
Earth fault
Emergency stop with key
USB to RS485 Communications device
Coolant heater
Battery
Low coolant level shutdown
Standby Pack (Smart Jacket water heater, Battery charger)
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8PF