3512 with Upgradeable Package

3512 with Upgradeable Package

Dry Weight - Genset (minimum)
22099 lb
Dry Weight - Genset (maximum)
22540 lb
Displacement
3161.03 in³
Height - Maximum
92 in

Generator Set Dimensions

Dry Weight - Genset (minimum)
22099lb
Dry Weight - Genset (maximum)
22540lb
Height - Maximum
92in
Length - Maximum
203.5in
Width - Maximum
79.3in

Engine Specifications

Displacement
3161.03in³
Bore
6.69in
Stroke
7.48in
Engine Model
3512A, V-12, 4-Stroke Water-Cooled Diesel
Bore
170 mm (6.69 in)
Displacement
51.8 L (3161.03 in3)
Stroke
190 mm (7.48 in)
Compression Ratio
13.5:1
Aspiration
TA
Governor Type
Woodward
Fuel System
MUI
Exhaust Flange Size - Internal Diameter
203.2 mm (8.0 in)
Air Inlet
Single element canister style with service indicator

Generator Set Specifications

Minimum Rating
890 eKW
Maximum Rating
1250 eKW
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Standard Equipment:

  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
  • Control Panel
    • Auto / start / stop control
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • kVAr-hr (total)
    • EMCP 4.2B
    • kVAr (per phase, average & percent)
    • Customer data link (Modbus RTU)
    • KVAR/PF modes, RFI suppression, min/max exciter
    • Overcurrent (50/51)
    • IVR includes reactive droop capability, 3-phase voltage sensing
    • Generator phase sequence
    • 6 programmable digital inputs
    • Engine cool-down timer
    • Limiter and exciter diode monitor
    • Over / under voltage (27/59)
    • Low coolant temperature
    • Generator set packages include Caterpillar's Voltage Regulator (IVR).
    • Accessory module data link
    • Low oil pressure
    • Over / under frequency (81 o/u)
    • Generator mounted - rear facing
    • Reverse reactive power (kVAr) (32RV)
    • Emergency stop
    • Lamp test
    • Overspeed
    • kVA (per phase, average & percent)
    • Operating hours
    • DC volts
    • Low coolant level
    • Programmable protective relaying functions:
    • Frequency (Hz)
    • Amps (per phase & average)
    • Environmental sealed front face
    • Failure to start (overcrank)
    • Power Factor (per phase & average)
    • Controls:
    • kW (per phase, average & percent)
    • Oil pressure (psi, kPa or bar)
    • 24-volt DC operation
    • 4 programmable relay outputs (Form A)
    • Emergency stop pushbutton
    • 2 programmable relay outputs (Form C)
    • RPM
    • Digital indication for:
    • Engine cycle crank
    • Speed adjust
    • Coolant temperature
    • 2 programmable digital outputs
    • Text alarm / event descriptions
    • Serial annunciator module data link
    • Communications:
    • kW-hr (total)
    • Volts (L-L & L-N)
    • Alarm acknowledge
    • Warning / shutdown with common LED indication of shutdowns for:
    • Reverse power (kW) (32)
    • High coolant temperature
  • Cooling System
    • Coolant level sensors. (Not included with packages without radiator)
    • Coolant drain line with valve
    • Fan and belt guards.
    • JWAC
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
  • Exhaust
    • Dry Exhaust Manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel priming pump
    • Fuel cooler; not included with packages without radiator
    • Secondary fuel filters
    • Flexible fuel lines - shipped loose
  • Generators And Attachments
    • Internal excitation or permanent magnet
    • Winding temperature detectors
    • 6 Lead
    • LV:
    • 60 Hz models: NEMA standard hole pattern
    • Busbar connections, top center mounted, top cable entry
    • 3 Phase brushless, salient pole
    • Random wound
    • NEMA Class H insulation
    • Class H temperature rise at 40C ambient (125C prime / 150C standby)
    • KVAR/PF modes
    • Exciter diode monitor
    • Caterpillar's Digital Voltage Regulator (CDVR) includes:
    • RFI suppression
    • Reactive droop capability
    • Min / max exciter limiter
    • Note: 1800 frames are form wound, permanent magnet, with winding temp detectors
    • Generator set packages include: Regulator (CDVR)
    • 3 Phase voltage sensing
  • Governing System
    • Woodward 2301A isochronous governor
  • Lube System
    • Fumes disposal
    • Lubricating oil
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
    • Integral lube oil cooler
    • Oil drain lines and valve
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Rubber anti-vibration mounts (shipped loose)
  • Starting / Charging System
    • 24-volt electric starting motor
    • Battery and battery rack w/cables
    • 50 Amp charging alternator
    • Battery disconnect switch
  • General
    • Flywheel and Flywheel housing-SAE No. 00
    • SAE Standard Rotation
    • RH Service
    • Paint - Caterpillar yellow with high gloss black rails & radiator

Optional Equipment:

  • Air Inlet System
    • Single stage air cleaners
    • Dual element air filters
  • Circuit Breakers
    • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated circuit breakers
  • Control Panels
    • Remote custom annunicator
    • CAN2 Network equipment
    • Modbus monitoring of packages
    • EMCP 4.3, EMCP 4.4
    • Local discrete I/O package
    • Vandle proof panel door
    • Cat connect
    • Load share module options
    • First local annunciator
  • Cooling System
    • Coolant
    • Water level gauge
    • Optional radiator arrangements
  • Exhaust System
    • Exhaust flexible fitting
    • Industrial grade (15 db) mufflers
    • Exhaust elbows
    • Exhaust Y adapters
  • Generators And Attachments
    • Space heater control
    • Space heater
    • Generator conversion
    • Space heater
    • Space heater control
    • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, permanent magnet, No. of leads = 6, pitch= 0.6667
    • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, form wound, permanent magnet, No. of leads = 6, pitch= 0.6667
  • Lube System
    • Oil level regulator
    • Lube oil
    • Primary fuel systems
    • Prelube sump pump
    • Oil level regulator
  • Special Tests / Reports
    • Genset tors vibration analysis
    • PGS test report @ 1.0 power factor
    • PKG factory test report
    • Standard genset TVA report
    • Standard engine test charge
    • Fuel consumption test
    • Generator test report
    • Standard engine test charge
    • PGS test report @ 0.8 power factor
    • PGS test report @ 1.0 power factor
    • Torsional vibration analysis
    • Generator test report
  • Crankcase System
    • Protection systems
    • Ventilation system
    • Protection systems
    • Ventilation system
  • Batteries And Battery Housing
    • Battery chargers - 10, 20 and 35 amp
    • 24 Volt battery set - Dry
    • Battery chargers - 10, 20 and 35 amp
    • 24 Volt battery set - Dry
  • Mounting System
    • Spring type vibration isolator
    • Puck style low efficiency lsolators
    • IBC vibration isolators
    • Spring type vibration isolator
  • Instrumentation
    • Pyrometer and thermocouples
  • Protection System
    • Explosion relief valve
  • Starting / Charging Systems
    • Oversize battery set
    • Jacket water heater
    • Electric starting motors
    • Jacket water heaters
    • 24 Volt dual electric starting motor
    • Starter covers
  • General
    • Barring devices
  • Power Connection System
    • Breaker power connections
    • EMCP voltage and current sensing groups
    • Center post busbar
  • Circuit Breaker - Lv Packages
    • Electronically operated circuit breakers
    • Right hand power connections