3516B Generator Set
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
|
|
|
|
-
Generator Set Dimensions
-
- Length - Maximum
- 274.2in
- Width - Maximum
- 90in
- Height - Maximum
- 92.9in
- Dry Weight - Genset (maximum)
- 33300lb
-
Generator Set Specifications
-
- Minimum Rating
- 1640 ekW
- Maximum Rating
- 1825 ekW
- Voltage
- 380 to 13800
- Frequency
- 60 Hz
- Speed
- 1800 rpm
-
Generator Set Configurations
-
- Emissions/Fuel Strategy
- Low Fuel Consumption
-
Engine Specifications
-
- Engine Model
- 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
- Compression Ratio
- 15.5:1
- Aspiration
- TA
- Governor Type
- Adem™4
- Compression Ratio
- 33300lb
- Fuel System
- Electronic unit injection
- Bore
- 6.69in
- Displacement - HD
- 4764.73in³
- Stroke - HD
- 8.46in
Standard Equipment:
-
- Air Inlet System
-
- Air cleaner, single element canister type
-
- Control System
-
- EMCP 4.2
- Emergency stop pushbutton
- 24 Volt DC operation
- Environmental sealed front face
- Text alarm / event descriptions
- Generator mounted - rear facing
- Generator set packages include Caterpillars Voltage
- Regulator (IVR) - IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter
- Limiter and exciter diode monitor
- Controls:
- Speed adjust
- Auto/start/stop control
- Engine cool-down timer
- Engine cycle crank
- Alarm acknowledge
- Lamp test
- Load histogram feature
- PLC functionality
- Customizable screens
- True RMS AC metering, 3-phase, +/-2% accuracy
- Digital indication for:
- RPM
- DC volts
- Operating hours
- Oil pressure (psi, kPa or bar)
- Coolant temperature
- Volts (L-L & L-N), frequency (Hz)
- Amps (per phase & average)
- Power Factor (per phase & average)
- kW (per phase, average & percent)
- kVA (per phase, average & percent)
- kVAr (per phase, average & percent)
- kW-hr (total)
- kVAr-hr (total)
- Warning / shutdown with common LED indication of shutdowns for:
- Low oil pressure
- High coolant temperature
- Overspeed
- Emergency stop
- Failure to start (overcrank)
- Low coolant temperature
- Low coolant level
- Programmable protective relaying functions:
- Generator phase sequence
- Over/Under voltage (27/59)
- Over/Under Frequency (81 o/u)
- Reverse Power (kW) (32)
- Reverse Reactive Power (kVAr) (32RV)
- Overcurrent (50/51)
- Communications:
- Customer data link (Modbus RTU)
- Accessory module data link
- Serial annunciator module data link
- Cat Connect
- 3 Analog inputs
- 6 Customer programmable digital inputs
- Number of I/O varies on options selected:
- 4 Programmable relay outputs (Form A)
- 1 Programmable relay outputs (Form C)
- 1 Programmable digital outputs
-
- Cooling System
-
- Package mounted radiator
-
- Exhaust System
-
- Dry exhaust manifold
- Flanged faced outlet(s)
-
- Fuel System
-
- Secondary fuel filters
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines - shipped loose
- Fuel priming pump
-
- General
-
- Paint - Caterpillar yellow except rails and radiators gloss black
- RH Service
- Flywheel and Flywheel housing-SAE No. 00
- SAE Standard Rotation
-
- Generators And Attachments
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
- 3 Phase brushless, salient pole
- 6 lead
- LV
- Random wound
- Permanent magnet
- Winding temperature detectors
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby) - 60 Hz models: NEMA standard hole pattern
- MV:
- Form wound
- Permanent magnet
- Winding temperature detectors
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby)
- Bus bar connections, right side extension box, bottom cable entry - 60 Hz models: NEMA standard hole pattern
- HV:
- Form wound
- Permanent magnet
- Winding temperature detectors
- Anti condensation space heater
- Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
-
- Governing System
-
- ADEM A3
-
- Lube System
-
- Lubricating oil
- Gear type lube oil pump
- Integral lube oil cooler
- Oil filter, filler and dipstick
- Oil drain lines and valve
- Fumes disposal
-
- Mounting System
-
- Rails - engine/generator/radiator mounting.
- Anti-vibration mounts (shipped loose).
- Rubber anti-vibration mounts (shipped loose)
-
- Starting System
-
- 24 Volt electric starting motor
- 45 Amp charging alternator
- Battery and battery rack w/cables
- Battery disconnect switch
Optional Equipment:
-
- Air Inlet System
-
- Single Element Filter
- Dual Element Air Cleaner
- Optional Radiator Arrangements
- Standard ambient radiators
- Standard ambient ATAAC radiators
-
- Control Panels
-
- EMCP 4.3, EMCP 4.4
- Generator main terminal box
- Load share module
- Digital I/O module
- Remote monitoring software
- Empty upper box
- Side extension box
- Cable Shroud
- Annunciator - local
- Annunciator - remote
- Vandal proof panel cover
-
- Cooling System
-
- Water level switch gauges
- Coolant
-
- Crankcase Systems
-
- Crankcase protection groups:
- No explosion relief valves
- Explosion relief valve
- Crankcase ventilation systems
-
- Exhaust System
-
- Elbows>
- Flange and exhaust expanders
- Flanges
- Flexible fittings
- Y Adapters
- Mufflers
- Exhaust offset
- Tier 4 lean emissions moduel
- Tier 4 dosing cabinet
- Tier 4 clean emission MOD kits
- Elean emission parts
-
- Extended Service Coverage
-
- Platinum, Silver and Gold coverage
-
- Fuel System
-
- Primary fuel filter
- Gas fuel filter
- Fuel priming pump (Tier 4)
-
- Generators And Attachments
-
- 1600 Frame - 380, 440, 480, 600 Volts, 3 Phase 1800 RPM, RW, IE, No. of leads = 6, Pitch = .6667
- 1600 Frame - 380, 440, 480, 600 Volts, 3 Phase 1800 RPM, RW, PM, No. of leads = 6, Pitch = .6667
- 1600 Frame - 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM ,FW, PM, No. of leads = 6, Pitch = .6667
- 1800 Frame
- Generators high voltage
- 2700 Frame - 6300, 6600, 6900 Volts, 3 Phase 1800 RPM, FW, PM, No. of leads = 6, Pitch = .6667
- 3000 Frame - 12470, 13200, 13800 Volts, 3 Phase 1800 RPM, FW, PM, No. of leads = 6, Pitch = .6667
- Space heater kit
- Generator conversions
- Hi volt optional attachments
- Alternator air cleaner
- Differential current transformers
-
- Instrumentation
-
- Pyrometer and Termocouples
-
- Lube System
-
- Lube oil in standard sump
- Oil level regulator
- Prelube pump groups
-
- Mounting System
-
- Puck style low efficiency isolators
- Spring type vibration isolators
- IBC vibration isolators
-
- Power Connections
-
- Grounding groups
- Neutral ground connections
- Center post busbar
- Right side power connections
- Cable entry - right side
- left side power connections
- Cable entry - left side
- Rear power connections
- Cable entry - rear
-
- Power Termination
-
- Circuit breakers - LV Packages
- 1600, 2000, 2500, 3000 and 4000 Amp, 3 Pole, UL-100% rated circuit breakers
- 2000, 2500, 3200 Amp, 4 Pole, IEC rated circuit breakers
- 2000, 2500, 3200 Amp, 3 Pole, IEC rated circuit breakers
-
- Special Tests / Reports
-
- Seismic certifications
- OSPD certification
- PGS test report @ 1.0 power factor
- PGS test report @ 0.8 power factor
- Standard engine test
- Generator set report
- Fuel consumption test
- Torsional vibration analysis
-
- Starting / Charging
-
- Engine barring devices
- Batteries, racks and cables
- 10, 20 and 35 Amp battery charger
- 50 Amp NFPA battery charger
- Electric starting motors
- Air starting motors
- Starter covers
- Air pressure regulator
- Jacket water heaters