Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Standby Rating 2000 kVA
Prime Power Rating 1825 kVA
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 380 to 11000 Volts
Duty Cycle Standby, Mission Critical, Prime, Continuous
Emissions/Fuel Strategy Low Fuel Consumption
Frequency 50 Hz
Maximum Rating 2000 kVA
Minimum Rating 1600 kVA
Prime Power Rating 1825 kVA
Speed 1500 rpm
Standby Rating 2000 kVA
Voltage 380 to 11000 Volts
Aspiration TA
Bore 6.69in
Compression Ratio 13.0:1
Displacement 4210.64in³
Engine Model 3516 TA, V-16, 4-Stroke Water-Cooled Diesel
Fuel System Mechanical unit injection
Governor Type Woodward
Stroke 7.48in
Dry Weight - Genset (maximum) 33900lb
Height - Maximum 93.2in
Length - Maximum 232.9in
Width - Maximum 90in
Air cleaner; single element canister type
Air cleaner
Package mounted radiator
Exhaust flange outlet
Secondary fuel filters
Fuel priming pump
Primary fuel filter with integral water separator
Matched to the performance and output characteristics of Cat engines
IP23 Protection
Busbar
EMCP 4 Genset controller
Over/under voltage (27/59)
Serial annunciator module data link
Communications:
Overcurrent (50/51)
Over/under frequency (81 o/u
Text alarm/event descriptions
Generator set packages include Caterpillar's voltage regulator
Programmable protective relaying functions:
4 Programmable relay outputs (Form A)
Reverse power (kW) (32)
Emergency stop
Amps (per phase & average)
Oil pressure (psi, kPa or bar)
Operating hours
24 Volt DC operation
Low oil pressure
6 Customer programmable digital inputs
1 Programmable digital outputs
1 Programmable relay outputs (Form C)
Volts (L-L & L-N)
Number of I/O varies on options selected
RPM - DC volts
Low coolant level
kVAr-hr (total)
Controls: Speed adjust - Auto/start/stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
kW-hr (total)
Failure to start (overcrank)
Environmental sealed front face
Power factor (per phase & average)
Accessory module data link
Generator mounted - rear facing
High coolant temperature
Overspeed
3 Analog inputs
Frequency (Hz)
Warning/shutdown with common LED indication of shutdowns for
Coolant temperature
IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min /max exciter. Limiter and exciter diode monitor
Customer data link (Modbus RTU)
kVA (per phase, average & percent)
Cat connect
Generator phase sequence
Reverse reactive power (kVAr) (32RV
DC volts
kW (per phase, average & percent)
kVAr (per phase, average & percent)
Emergency stop pushbutton
Digital indication for:
Low coolant temperature
EMCP 4.2B
Certified standard PGS provided
Flanged faced outlet(s)
Dry exhaust manifold
Flexible fuel lines - shipped loose
Fuel priming pump
Fuel cooler; not included with packages without radiator
Secondary fuel filters
SAE standard rotation
Flywheel and flywheel housing - SAE No. 00
Right hand servicing
Caterpillar yellow with high gloss black rails and radiator
Medium voltage:
Form wound
Winding temperature detectors
High voltage:
3 Phase brushless, Salient pole
Permanent magnet excitation (PMG)
Permanent magnet excitation (PMG)
NEMA standard hole pattern
Internal excitation (IE)
Six lead
Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
Low voltage:
Winding temperature detectors
NEMA standard hole pattern
Form wound
Winding temperature detectors
Random wound
Busbar connections, top center mounted, top cable entry
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
Anti-condensation space heater
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
ADEM A3
Parts book
Gear type lube oil pump
Fumes disposal
Oil drain lines and valve
Lubricating oil
Oil filter, filler and dipstick
Integral lube oil cool
Anti-vibration mounts (shipped loose)
Rubber anti-vibration mounts - shipped loose
Rails - Engine/generator/radiator mounting
Battery disconnect switch
Battery and battery rack w/cables
45 Amp Charging alternator
24 Volt electric starting motor
Dual element air cleaner
Single element filter
Exhaust mufflers
Optional installed radiators
Coolant
Standard ambient ATAAC radiators
Optional installed ATAAC radiators
Standard ambient radiators
Water level switch gauges
Internal excitation (IE)
Anti-condensation heater
Oversize and premium generators
Permanent magnet excitation (PMG)
No explosion relief valves
Ventilation system
Explosion relief valves
Circuit breakers, UL listed
Circuit breakers, IEC compliant
Remote monitoring software
Generator temperature monitoring & protection
Load share module
Digital I/O module
EMCP 4.2B
Exhaust offset
Tier 4 dosing cabinet
Flexible fittings
Mufflers
Tier 4 clean emissions module
Elbows
Flange and exhaust expanders
Tier 4 clean emission MOD Kits
Flanges
Clean emission parts
Y Adapters
Spring type vibration isolators
IBC isolators
Rubber anti-vibration mounts
Fuel priming pumps (Tier 4) - Manual or electric
Primary fuel filter
Jacket water heater
Oversize batteries
Battery chargers
Air starting motor with control and silencer
Heavy duty starting system
Charging alternator
Special paint (Colors other than Caterpillar yellow or high performance paints)
US aid emblem
Thermostat for space heater
Alternator air cleaner
Differential current transformers (DCT)
Differential current transformers (DCT) 8.7 kV and 15 kV classes
Generator conversion
Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
Space heater
Pyrometer and thermocouples
Oil level regulator
Prelube pumps
Lube oil in standard sump
Spring type vibration isolators
Puck style low efficiency isolators
IBC vibration isolators
Neutral ground connections
Center post busbars
Right side power connections
Rear power connections
2700 Frame, four lead, four terminal
Left side power connections
Ground cables between generator and terminal box
Low voltage Circuit breakers
IBC Certification
Standard engine test charge
PGS Test report @ 1.0 power factor
Generator test report
Fuel consumption test
Canadian Standards Association certification
PGS Test report @ 0.8 power factor
OSHPD Certification
Torsional vibration analysis reports
Generator set fuel consumption test
Electric starting motors
Air pressure regulator
24 Volt battery set - Dry
Engine barring device
Starter cover
Air starting motors
Jacket water heaters
10, 20, 35 and 50 Amp Battery chargers
Platinum, Gold and Silver coverage