ATC-800 CONTROLLER

ATC-800 CONTROLLER

The ATC-900 C9ontroller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-800 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

  • Rating Range 120 to 600V, single phase and three phase @ 50/60 Hz

  • Transfer Type Switch application dependent

  • Switch Type Switch application dependent

  • Input Control Voltage 120Vac (50/60 Hz) (operating range 65 to 160 Vac)

Request a quote

Product Specifications

Specifications

Technical Summary

  • Rating Range 120 to 600V, single phase and three phase @ 50/60 Hz

  • Switch Type Switch application dependent

  • Transfer Type Switch application dependent

ATC Controller Specifications

  • Enclosure Compatibility

  • NEMA 12 (std mounting)
  • NEMA 3R
  • UV Resistant Faceplate
  • Frequency Measurement Accuracy +/- 0.1 Hz

  • Frequency Measurement Range 40 Hz to 80 Hz

  • Frequency Measurements Of Source 1 and Source 2

  • Input Control Voltage 120Vac (50/60 Hz) (operating range 65 to 160 Vac)

  • Operating Humidity Up to 90% Relative Humidity (non-condensing)

  • Operating Temperature Range -20 to 70 degree C (-4 to +158 degree F)

  • Overfrequency Dropout Range 103 to 110% of Nominal System Frequency

  • Overfrequency Pickup Range 101% to (Dropout +1 Hz) of nominal system frequency

  • Underfrequency Dropout Range 90 to 97% of Nominal System Frequency

  • Underfrequency Pickup Range (Dropout +1 Hz) to 99% of Nominal System Frequency

  • Undervoltage Dropout Breaker Style 50 to 97% of Nominal System Voltage
    Contactor Style - 78 to 97%

  • Undervoltage Pickup (Dropout +2%) to 99% of Nominal System Voltage

  • Voltage Measurement Accuracy +/-1% of full scale

  • Voltage Measurement Range 0 to 700 Vac

  • Voltage Measurements of Utility Source 1, Source 2 and Load
    (VAB, VBC, VCA for Three Phase System)

Ratings

  • System Voltage Application 120 to 600 Vac (50/60 Hz) (single or three phase)