Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Maximum Rating 400 ekW
Minimum Rating 320 ekW
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 380 to 415 Volts
Duty Cycle Standby, Prime
Emissions/Fuel Strategy Low Fuel Consumption
Frequency 60 Hz
Maximum Rating 400 ekW
Minimum Rating 320 ekW
Speed 1800 rpm
Voltage 380 to 415 Volts
Aspiration Air to Air Aftercooled
Bore 5.12in
Compression Ratio 16.3:1
Displacement 762.8in³
Engine Model C13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Fuel System MEUI
Governor Type Adem™A4
Stroke 6.18in
Height - Maximum 84in
Length - Maximum 186.7in
Width - Maximum 79.3in
Aftercooler core
Air cleaner; light duty with disposable paper filter
Turbocharger
GCCP 1.3
Caterpillar extended life coolant
Coolant drain line with valve
Fan drive, battery charging alternator drive
Radiator and cooling fan with guard
Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
Base, formed steel with single wall integral 8-hour fuel tank
Standard open set fuel tank/base supplied
Segregated low voltage (AC/DC) wiring panel
Power center, IP22
Integrated voltage regulator (IVR)
Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
A Frame generator - IP21 Protection
Optional LC Frame generator - IP23 Protection
Cat electronic governor (ADEM A4)
Service indicator
Radiator package mounted
Low coolant level sensor
Coolant drain line with valve
Coolant level sight gauge
Disposable air filter
Lubricating oil
Oil drain valves
Oil cooler
Captive linear vibration isolators between base and engine-generator
Includes lifting provisions and termination points for coolant and lube oil drain lines
24V battery with rack and cables
Engine and alternator pre-paint, Caterpillar yellow
EU Certificate of Conformance (CE)
Global Certification for CIS
Single element air cleaner
Dual element air cleaner
4 Pole (IEC-100% rated) Circuit breaker
Circuit breaker (IEC) Auxiliary contacts
4 Pole (IEC-100% rated) Circuit breaker - Motorised
Padlockable circuit breaker device
Power terminal strip
Shunt trip for IEC circuit breaker
3 Pole (IEC-100% rated) Circuit breaker
3 Pole (IEC-100% rated) Circuit breakers - Motorised
GCCP 1.4
Local alarm modules: Local annunciator
Volt free contacts
Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
Remote annunciator module
Stone guards
Radiator duct flange
Low coolant temperature alarm
Sound attenuated enclosures
High ambient sound attenuated enclosures
6 and 8 inch elbow kit
Flexible 8 inch exhaust fittings
6 and 8 inch flange GP
Mufflers - End in/end out
10, 25 and 35 dBA attenuation
Manual fuel transfer pump
Integral dual wall fuel tank base
Fuel transfer system controls
Permanent magnet excitation (PMG) generator
LC frame generator
LC CIP generator
A Frame CIP generator
A Frame oversize generator
Ingress protection
Space heaters
Manual sump pump
Narrow skid base
5 Amp single Battery charger
Jacket water heater
Battery disconnect switch