Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Maximum Rating 60.0 ekW
Minimum Rating 27.0 ekW
Emissions/Fuel Strategy EU Stage II & R96/EUIIIa
Voltage 110 to 480 Volts
Duty Cycle Standby, Prime
Emissions/Fuel Strategy EU Stage II & R96/EUIIIa
Frequency 60 Hz
Maximum Rating 60.0 ekW
Minimum Rating 27.0 ekW
Speed 1800 rpm
Voltage 110 to 480 Volts
Aspiration Turbocharged
Bore 4.1in
Compression Ratio 17.25:1, 19.25:1
Displacement 201.4in³
Engine Model Cat® C3.3
Fuel System Direct Injection
Governor Type Mechanical
Stroke 5in
Height - Maximum 53.6in
Length - Maximum 43.9in
Width - Maximum 38.2in
Air cleaner; light duty with disposable element
GCCP 1.3
Coolant drain line with valve
Caterpillar extended life coolant
Radiator and cooling fan with guards
Fan drive, battery charging alternator drive
Stub pipe, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
Standard open set fuel tank/base supplied
Base, formed steel with single wall integral 8-hour fuel tank
Circuit breaker, IEC, 3 pole, mounted in tower panel
IP23 Protection
Tower panel, IP22, bottom cable entry
12 Leads
Voltage regulator (single phase sensing)
Segregated low voltage (AC/DC) wiring panel
Mechanical governing system - model dependant
Mechanical and electrical governing system - model dependant
Lubricating oil
Oil drain line with valve
includes lifting provisions and termination points for coolant
Includes lifting provision and drag points
Termination points for coolant and lube oil drain lines
Captive linear vibration isolators between base and engine-generator
12V Battery with rack & cables
Engine and alternator pre-paint, Caterpillar yellow
LC Frame alternator
Anti-condensation heater
Permanent magnet excitation (PMG)
LC Frame alternator with coastal protection
R Frame auxilliary winding
Alternator removal options
4 Pole Circuit breaker to 250A
Padlockable breaker device
GCCP 1.3
Overload shutdown via breaker
Volt free contacts
Earth leakage (2 wire only)
Speed adjust potentiometer
Voltage adjust potentiometer
Battery charger
Control panel heater
Earth fault (2 wire only)
Panel mounted audible alarm
Emergency stop with key
Coolant heater
Low coolant level shutdown
Low coolant temperature alarm
European upgrade to STD set for "CE"
Global certification for CIS
CEE for sockets for enclosure
Socket blanking plate
Sound attenuated level 1 enclosure (GALV)
Sound attenuated level 2 enclosure CE
Rental pack (CAE only)
Skidbase for CALG enclosure sets
Low fuel level shutdown
High fuel level alarm
Compact skidbase for open sets
Low fuel level alarm
Bunded fuel tank
Open set narrow tankbase
Silencer installation kit
Battery removal
Electronic governor
Residential silencer
External single point lift - enclosure
PGS Test report @ 0.8 power factor
PGS Test report @ 1.0 power factor
Stone guards/rad trans flange
Packing case - compact set
Packing case - canopied set