Engine Paralleling and Integration Control (EPIC)

Engine Paralleling and Integration Control (EPIC)

The Engine Paralleling and Integration Control (EPIC) product line provides standard paralleling controls in a remote cabinet separate from the engine generator set and separate from switchgear (breakers and bus).

  • Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)

  • Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)

  • Application LV and MV (208V-27kV)

  • ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Request a quote

Product Specifications

Specifications

Technical Summary

  • Application LV and MV (208V-27kV)

  • Configuration Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)

  • Modes of Operation Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)

Generator Protective Devices

  • ANSI Protective Devices 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

  • ANSI Protective Devices 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

  • Certifications UL / cUL 508A

  • Control Panel Enclosure NEMA 12

  • Operating Temperature 0°C to 55°C

  • Storage Temperature -20°C to 60°C

Features

Equipment

Standard Equipment

  • Allows user to return sysem to automatic in the event of a touchscreen failure

Optional Equipment

  • With breaker position indications and circuit breaker control switch

  • With utility close lockout switch, breaker position indications, and circuit breaker control switch

  • Provides additional discrete synchronization protection

  • Accommodates interface with a building management system

  • An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity