List Rates
Online rates are currently unavailable. Please contact this store for more details.G3512 750kW Gas Generator Set
|
|
|
|
Generator Set Specifications
Engine Specifications
-
Aspiration TA
-
Bore 6.7in
-
Displacement 3173in³
-
Engine Model G3512
-
Governor Type ADEM A4
-
Stroke 7.5in
Generator Set Dimensions
-
Height 99.4in
-
Length 205.7in
-
Weight 27500lb
-
Width 90in
Standard Equipment
-
Dual air cleaners, 1 per side, with service indicator
-
Two-element single-stage air cleaner with enclosure and service indicator
-
Cat ECS 100
-
Engine driven pumps for jacket water and separate circuit aftercooler
-
Jacket water and SCAC engine-driven pumps
-
Jacket water and SCAC thermostats
-
LH or RG connections when radiator is not selected
-
Package mounted radiator
-
NOx sensor based air-fuel-ratio control
-
0.5 to 5 psi engine fuel inlet pressure
-
Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
-
Gas Train: NFPA37 and CSA B149.3
-
Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
-
Dry exhaust manifolds, insulated and shielded
-
Cat-flanged face outlet on turbocharger
-
Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
-
Throttle plate, 24V DC actuator, controlled by GECM
-
Engine-installed electronic control valve
-
Gas pressure regulator
-
24V DC energized-to-run (ETR) gas shutoff valve
-
Crankshaft vibration damper and guard
-
Operation and maintenance manuals
-
Parts book
-
Paint- Caterpillar Yellow except rails and radiators gloss black
-
RH Service
-
Gear type lube oil pump
-
Cartridge style oil filter
-
Anti-condensation space heater
-
Winding temperature detectors
-
NEMA Class H insulation
-
SR5
-
Permanent Magnet Excitiation
-
Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
-
ADEM A4
-
Individual Cylinder Detonation Sensitive Timing (DST)
-
Electronic Ignition System (controlled by ADEM A4)
-
ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input
-
24V DC starting motors
-
Batteries with rack and cables
-
Electric Starter
Optional Equipment
-
Mounting brackets and piping
-
Air cleaner with precleaner
-
S LSI, G LSIG, P LSIG-P, 4th Digit Type
-
Right, left, rear mounted
-
1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
-
1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
-
2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
-
100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
-
3-pole (IEC 947-2 rated)
-
Frame mounting
-
Remote annunciator
-
Local alarm module
-
Local PC monitoring
-
Engine failure relay
-
Remote PC monitoring
-
Coolant level drain line with valves, fan with guard
-
Remote radiator for JW and SCAC circuits, level switch included but not wired
-
Inlet/Outlet connections
-
305 mm (12in.) elbow
-
18, 25 dBA Attenuation
-
Flexible fittings
-
305 mm (12 in.) muffler
-
305mm (12 in) spark arresting muffler
-
305 mm (12 in.) flange
-
3, 0-100 kPag, 4-20mA gas train pressure sensors
-
Special paint order
-
US AID emblem
-
Tool set
-
Digital diagnostic tool
-
Cable access box
-
Generator air filter
-
European bus bars
-
Low voltage extension box
-
Bearing temperature detectors
-
20A, 24VDC battery charger
-
Battery with cables and rack
-
Jacket water heater
-
45A, 24V charging alternator (requires engine driven pumps)
-
60 Hz: USA
*Images are for general reference only. Individual product models may vary. Please consult with your dealer to verify machine configuration.
Displacement 3173in³
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset
Frequency 60 Hz
Fuel Type Natural Gas, Hydrogen Blend (up to 5%)
Gas Standby Rating 750 ekW @ 0.8pf
RPM 1800 rpm