Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Standby Rating 1750 ekW
Prime Power Rating 1600 ekW
Emissions/Fuel Strategy U.S. EPA Cert., Tier 2
Voltage 380 to 13800 Volts
Duty Cycle Standby, Mission Critical
Emissions/Fuel Strategy U.S. EPA Cert., Tier 2
Frequency 60 Hz
Maximum Rating 1750 ekW
Minimum Rating 1600 ekW
Prime Power Rating 1600 ekW
Speed 1800 rpm
Standby Rating 1750 ekW
Voltage 380 to 13800 Volts
Aspiration TA
Bore 6.69in
Compression Ratio 14.7:1
Displacement 3574in³
Engine Model 3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel
Fuel System Electronic unit injection
Governor Type ADEM™ A3
Stroke 8.46in
Dry Weight - Genset (maximum) 32660lb
Height - Maximum 110in
Length - Maximum 262.9in
Width - Maximum 89.8in
Air cleaner; single element canister type with service indicator
Package mounted radiator
Exhaust flange outlet
Primary fuel filter with integral water separator
Fuel priming pump
Secondary fuel filters
Matched to the performance and output characteristics of Cat engines
IP23 Protection
Busbar
Cat ECS Genset controller
Generator set packages include Caterpillar's voltage regulator (IVR). IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min/max exciter. Limiter and exciter diode monitor
Emergency stop pushbutton
Oil pressure (psi, kPa or bar)
1 Programmable digital outputs
Accessory module data link
4 Programmable relay outputs (Form A)
kVAr-hr (total)
Reverse power (kW) (32)
kVAr (per phase, average & percent)
Amps (per phase & average)
Over/under frequency (81 o/u)
Cat ECS 100
PLC functionality
1 Programmable relay outputs (Form C)
Programmable protective relaying functions:
RPM
Frequency (Hz)
Low coolant level
Number of I/O varies on options selected
Lamp test
kVA (per phase, average & percent)
Emergency stop
kW (per phase, average & percent)
Engine cool-down timer
Speed adjust
Generator phase sequence
Over/under voltage (27/59)
Warning/shutdown with common LED indication of shutdowns for:
Customer data link (Modbus RTU)
Volts (L-L & L-N)
High coolant temperature
Engine cycle crank
True RMS AC metering, 3-phase, +/-2% accuracy
Low coolant temperature
Low oil pressure
Cat connect
Digital indication for:
Communications
Environmental sealed front face
Reverse reactive power (kVAr) (32RV)
24 Volt DC operation
Power factor (per phase & average)
Overspeed
Auto/start/stop control
Load histogram feature
Controls:
Failure to start (overcrank)
Customizable screens
kW-hr (total)
Text alarm/event descriptions
Alarm acknowledge
Overcurrent (50/51)
Generator mounted - rear facing
Coolant temperature
DC volts
ADEM III
SCAC
Fan and belt guards
Caterpillar extended life coolant (Not included with packages without radiator, installed SF44CTS
Coolant level sensors (Not included with packages without radiator)
Radiator fan and fan drive
Coolant drain line with valve
Flanged faced outlet(s)
Dry exhaust manifold
Secondary fuel filters
Fuel priming pump
Fuel cooler; not included with packages without radiator
Flexible fuel lines - shipped loose
Random wound
Permanent magnet excitation (PMG)
High voltage
Six lead
NEMA standard hole pattern
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime/150C standby)
Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
NEMA standard hole pattern
Winding temperature detectors
NEMA standard hole pattern
Internal excitation (IE)
Form wound
3 Phase brushless, Salient pole
Busbar connections, right side extension box, bottom cable entry
Low voltage:
Busbar connections, top center mounted, top cable entry
Medium voltage:
Parts book
Oil drain lines and valve
Lubricating oil
Oil filter, filler and dipstick
Fumes disposal
Gear type lube oil pump
Integral lube Oil cooler
Rubber anti-vibration mounts - shipped loose
Battery and battery rack w/cables
45 Amp Charging alternator
24 Volt electric starting motor
Battery disconnect switch
Paint - Caterpillar yellow except rails and radiators gloss black
SAE standard rotation
Right hand servicing
Flywheel and Flywheel housing-SAE No. 00
Paint - Caterpillar yellow with high gloss black rails & radiator
Digital I/O module
EMCP 4.4
Load share module
Remote monitoring software
Generator temperature monitoring & protection
Exhaust mufflers
Heavy duty air cleaner
Single element filter
Permanent magnet excitation (PMG)
Anti-condensation heater
Internal excitation (IE)
Oversize and premium generators
Circuit breakers, IEC compliant
Circuit breakers, UL listed
Standard installed radiators
Standard installed ATAAC radiators
Optional installed ATAAC radiators
Water level switch gauges
Coolant
Optional installed radiators
Flanges
Flange and exhaust expanders
Flexible fittings
Elbows
Y Adapters
Mufflers
Primary fuel filter
Heavy duty starting system
Charging alternator
Battery chargers
Oversize batteries
Air starting motor with control and silencer
Jacket water heater
1400, 1600, 2700 Frames
Space heater
Generator conversion from IE to PM
Differential current transformers (DCT) 15 kV class
RW, IE, 6 Leads, Pitch 0.6667
Generator air cleaner
Low voltage: 380,440 / 480 Volts, 3 Phase, 1800 rpm
Differential current transformers (DCT) 8.7 kV class
Wiring GP W/O cyl sensors
Pyrometer and thermocouples
Oil drains
Lubrication oil in standard sump
Oil level regulator
Prelube pumps
US aid emblem
The following options are based on regional and product configuration:
Automatic transfer switches (ATS)
EU Certificate of Conformance (CE)
CSA Certification
Integral & sub-base UL listed dual wall fuel tanks
EEC Declaration of Conformity
UL 2200 package
Integral & sub-base fuel tanks
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
Enclosures: Sound attenuated, weather protective
Crankcase ventilation system
No explosion relief valves
No crankcase explosion relief valves
Explosion relief valves
Spring type vibration isolators
IBC vibration isolators
Puck style low efficiency isolators
IBC isolators
Rubber anti-vibration mounts
Spring type vibration isolators
1600 ,2000, 2500, 3000, 4000 Amp, 3 Pole, UL-100% rated Circuit breakers
Grounding groups
Neutral ground connections
Right side power connections
Rear power connections
Left side power connections
Six lead, six terminal option
2000, 2500, 3200 Amp, 3 Pole, IEC rated Circuit breakers
Center post busbars
2000, 2500 Amp, 4 Pole, IEC rated Circuit breakers
Cable entry - right side
Fuel consumption test
Generator test report
IBC seismic Certification
PGS Test report @ 1.0 power factor
Standard engine test charge
CSA Certification
Generator fuel consumption test
Torsional vibration analysis
PGS Test report @ 0.8 power factor
24 Volt battery set - Dry
Air pressure regulator
10 Amp Battery charger
Air starting motor
35 Amp Battery charger
Jacket water heaters
Starter cover
Engine barring device
Batteries, racks and cables:
Electric starting motors