C175-20

C175-20

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

  • Standby Rating 4000 (no fan)/3900/3620(no fan)/3500 ekW

  • Prime Power Rating 3600 (no fan)/3500/3300 (no fan)/3180 ekW

  • Emissions/Fuel Strategy Low Fuel, Tier 2

  • Voltage 480 to 13800 Volts

Request a quote

Product Specifications

Specifications

Generator Set Specifications

  • Duty Cycle Standby, Mission Critical, Prime, Continuous

  • Emissions/Fuel Strategy Low Fuel, Tier 2

  • Frequency 60 Hz

  • Maximum Rating 4000 ekW

  • Minimum Rating 3150 ekW

  • Prime Power Rating 3600 (no fan)/3500/3300 (no fan)/3180 ekW

  • Speed 1800 rpm

  • Standby Rating 4000 (no fan)/3900/3620(no fan)/3500 ekW

  • Voltage 480 to 13800 Volts

Engine Specifications

  • Aspiration Turbo Aftercooled

  • Bore 6.89in

  • Compression Ratio 15.3:1

  • Displacement 6456.31in³

  • Engine Model C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel

  • Fuel System Common Rail

  • Governor Type ADEM� A4

  • Stroke 8.66in

Generator Set Dimensions

  • Dry Weight - Genset (maximum) 66200lb

  • Dry Weight - Genset (minimum) 55100lb

  • Height - Maximum 150.7in

  • Height - Minimum 87.6in

  • Length - Maximum 330.6in

  • Length - Minimum 261.5in

  • Width - Maximum 127.7in

  • Width - Minimum 85.4in

Features

Equipment

Standard Equipment

  • 4 x Single element air cleaner canisters with service indicator(s).

  • 24 Volt DC operation

  • 4 Programmable relay Inputs

  • 4 Programmable relay output

  • Alarm acknowledge

  • Amps (per phase & average)

  • Auto/start/stop control

  • Coolant temperature

  • DC volts

  • Digital indicators

  • Cat ECS 100

  • Emergency stop

  • Emergency stop pushbutton

  • Engine cool-down timer

  • Engine cycle crank

  • Environmental sealed front face

  • Failure to start (overcrank)

  • Frequency (Hz)

  • High Coolant temperature

  • Lamp test

  • Low coolant level

  • Low oil pressure

  • Oil pressure (psi, kPa or bar)

  • Operating hours

  • Overspeed

  • RPM

  • Speed adjust

  • Text alarm/event descriptions.

  • True RMS AC metering, 3-phase, +/-2% accuracy

  • Volts (L-L & L-N)

  • Wall mounted controls:

  • Warning/shutdown Indicators:

  • AC Inlet: 6" ANSI / AC Outlet: 3-1/2" ANSI

  • Coolant sensors

  • JW Inlet: 6" ANSI / JW Outlet: 5" Cat Flange

  • SCAC cooling

  • Dry exhaust manifold

  • Dual ANSI 18" / DIN 450 flanges. Shipped loose. Support required from installation

  • 10 Micron spin on yype

  • 4 Micron spin on type

  • Engine mounted filters x 3

  • Filters x 3

  • Primary fuel filter water/fuel water separator

  • Secondary/tertiary fuel filters

  • 3 Phase brushless

  • 3 Phase voltage sensing

  • 6 Leads

  • Anti-condensation space heater

  • Class H temperature rise at 40C ambient

  • Exciter diode monitor

  • Form wound

  • IEC platinum stator RTDs

  • Min / max exciter limiter

  • NEMA Class H insulation

  • Permanent magnet excitation (PMG)

  • Reactive droop capability

  • RFI suppression

  • Right side extension box, bottom cable entry

  • Salient pole

  • Voltage regulator

  • ADEM A4

  • Redundant shutdown (Overspeed protection through a duplicate speed sensing system)

  • Fumes disposal

  • Gear type lube oil pump

  • Integral lube Oil cooler

  • Lubricating oil

  • Oil drain lines and valve

  • Oil filter, filler and dipstick

  • Rails - Engine/generator

  • Rubber anti-vibration mounts - shipped loose

  • Batteries and battery rack w/cables

  • Battery disconnect switch

  • Dual 24 volt electric starting motors

  • Paint - Caterpillar yellow with high gloss black rails

  • Right hand servicing

  • SAE standard rotation

Optional Equipment

  • Single element air cleaner

  • EMCP 4.4

  • Controller and MV and HV power connection locations

  • Controller voltage and current sensing groups

  • E-Stop

  • Generator harness

  • Generator temperature monitoring

  • Interconnect harness

  • Load share module

  • Modbus monitoring of packages

  • Speed adjust

  • Vandal proof panel door

  • Annunciator modules

  • Customer interface options

  • Fuel cooler

  • Package mounted radiators

  • Remote radiators

  • Crankcase ventilation system

  • Explosive relief valves

  • Exhaust collectors/manifold

  • Front housing - Prime or continuous

  • Front housing - Standby or mission critical

  • Mufflers (15, 25 and 34 dBA silencers)

  • Primary fuel filter

  • Anti-condensation heater

  • Internal excitation (IE)

  • Oversize and premium generators

  • Permanent magnet excitation (PMG)

  • Differential current transformers

  • Generator air cleaner

  • Medium voltage - 3000 Frames - 60 Hz, 3 phase, 1800 rpm, FW, PM, No of leads=6, Pitch 0.6667

  • Thermostat for space heater

  • Pyrometer and thermocouples

  • Drain group oil pans

  • Electric prelube pumps

  • Lube oil heater

  • Lubricating oil

  • Oil filters

  • IBC vibration isolators - Shipped loose

  • Rubber anti-vibration mounts

  • Spring type linear vibration isolators

  • Circuit breakers, IEC compliant

  • Circuit breakers, UL listed

  • Custom generator TVA report

  • Generator test report

  • Genset fuel consumption test

  • PGS Test report @ 0.8 power factor

  • PGS Test report @ 1.0 power factor

  • Special test charge - Engine only

  • Standard engine test charge

  • Standard genset TVA (Torsional Vibration Analysis) report

  • 20 Amp Battery chargers

  • 24 Volt battery set - Dry

  • 24 Volt electric starting motor

  • 35 Amp Battery chargers

  • 50 Amp Battery chargers

  • Air pressure regulator

  • Air starting motor

  • Charging alternators - Dry

  • Jacket water heaters

  • Starter location covers

  • Barring groups:

  • Control GP - air powered bar group

  • Engine air powered

  • Engine barring group

  • Manual

  • Special paint - 3500