DG400-2 (Three phase)

Compression Ratio
10.0:1
Compression Ratio
10.0:1
Voltage
120/208, 120/240, 277/480, 346/600 VAC
Frequency
60 Hz

Engine Specifications

Compression Ratio
10.0:1
Engine Model
G21.9L spark-ignited
Fuel System
Carburetor, Down Draft
Governor Type
Electronic
Aspiration
Turbocharged - Aftercooled
Bore
5.03in
Stroke
5.6in

Generator Set Specifications

Compression Ratio
10.0:1
Voltage
120/208, 120/240, 277/480, 346/600 VAC
Frequency
60 Hz
Natural Gas Rating
400 ekW
RPM
1800 rpm
Emissions/Fuel Strategy
U.S. EPA Certified for Stationary Emergency Application
Fuel Type
Natural Gas
Displacement
1336.42in

Generator Sets Specifications

Compression Ratio

Generator Set Dimensions

Length
154.4in
Width
71in
Height
67in
Weight
8429lb

Standard Equipment:

  • Cooling
    • Closed coolant recovery system
    • Factory-installed radiator
    • 50/50 Ethylene glycol antifreeze
  • Fuel
    • Low fuel pressure switch
    • Primary and secondary fuel shut-off
    • Fuel pressure test po
  • Generator
    • Class H insulation material
    • Full load capacity alternator
    • Permanent magnet excitation
  • Controls
    • EMCP 4.2 Series generator set controller
  • Mounting
    • Vibration isolaton (puck type)
  • Electric Starting And/or Prelube
    • Engine electrical system
    • Solenoid activated starter motor
    • Battery cables
  • Electric Power - Package Serial Number Prefix
    • Battery charging alternator

Optional Equipment:

  • Generator
    • Anti-condensation heater
    • Shunt trip and auxiliary contact breaker
    • Thermal magnetic or electronic trip MCCBs