Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Standby Rating 3365(no fan)/3250/3100(no fan)/3000 ekW
Prime Power Rating 3115(no fan)/3000/2825(no fan)/2725 ekW
Emissions/Fuel Strategy Low Fuel, Tier 2
Voltage 480 to 13800 Volts
Duty Cycle Standby, Mission Critical, Prime, Continuous
Emissions/Fuel Strategy Low Fuel, Tier 2
Frequency 60 Hz
Maximum Rating 3365 ekW
Minimum Rating 2500 ekW
Prime Power Rating 3115(no fan)/3000/2825(no fan)/2725 ekW
Speed 1800 RPM
Standby Rating 3365(no fan)/3250/3100(no fan)/3000 ekW
Voltage 480 to 13800 Volts
Aspiration Turbo Aftercooled
Bore 6.89in
Compression Ratio 16.7:1
Displacement 6456.31in³
Engine Model C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel
Fuel System Common Rail
Governor Type ADEM� A4
Stroke 8.66in
Dry Weight - Genset (maximum) 50500lb
Dry Weight - Genset (minimum) 42750lb
Height - Maximum 134.3in
Height - Minimum 87in
Length - Maximum 312.9in
Length - Minimum 241.6in
Width - Maximum 113.7in
Width - Minimum 83.1in
4 x Single element canister with service indicator(s).
2 Programmable relay outputs (Form C)
Low coolant level
Over/under voltage
Coolant temperature
Serial annunciator module data link
Alarm acknowledge
Text alarm/event descriptions
Volts (L-L & L-N)
Reverse power
Over/under frequency
Environmental sealed front face
Programmable protective relaying functions
Speed adjust
Generator phase sequence
Low coolant temperature
Generator mounted - rear facing
Overspeed
Controls
Frequency (Hz)
Engine cycle crank
Engine cool-down timer
Warning/shutdown Indicators:
Lamp test
2 Programmable digital outputs
6 Programmable digital inputs
High coolant temperature
Customer data link (Modbus RTU)
Auto/start/stop control
Emergency stop pushbutton
RPM
Digital Indicators
Communications
Accessory module data link
Oil pressure (psi, kPa or bar)
Low oil pressure
Overcurrent
Emergency stop
24 Volt DC operation
4 Programmable relay outputs (Form A)
Failure to start (overcrank)
True RMS AC metering, 3-phase, +/-2% accuracy
Power factor (per phase & average)
Operating hours
DC volts
Amps (per phase & average)
Cat ECS 100
Reverse reactive power
Bolted flange, with bellow for each turbo
Exhaust flange outlet
Engine mounted filters #REF!
Filters x 3
10 Micron spin on yype
Secondary/tertiary fuel filters
4 Micron spin on type
Primary fuel filter water/fuel water separator
Right side extension box, bottom cable entry
IEC platinum stator RTDs
Reactive droop capability
3 Phase voltage sensing
(MV) Busbar connections, right side extension box, bottom cable entry
Class F temperature rise at 40C ambient
Anti-condensation space heater
NEMA Class H insulation
6 Leads
Class H temperature rise at 40C ambient
Voltage regulator
Exciter diode monitor
Form wound
RFI suppression
(LV) Busbar connections, top/center mounted, top cable entry
3 Phase brushless
60 Hz models: NEMA standard hole pattern
Permanent magnet excitation (PMG)
Min / max exciter limiter
Salient pole
Redundant shutdown (Overspeed protection through a duplicate speed sensing system)
ADEM A4
Oil filter, filler and dipstick
Integral lube Oil cooler
Oil drain lines and valve
Fumes disposal
Lubricating oil
Prelube - required with prime, continuous, and standby
Gear type lube oil pump
Rails - Engine/generator
Rubber anti-vibration mounts - shipped loose
Dual 24 volt electric starting motors
Battery disconnect switch
Batteries and battery rack w/cables
Busbar
Two PM inspections
Paint - Caterpillar yellow with high gloss black rails & radiator
SAE standard rotation
LH Service
Flywheel and flywheel housing-SAE No. 00
Air inlet adapters
Dual element air cleaner
Single element air cleaner
Air inlet protection
Package mounted radiator
Automatically selected ground
Customer AC-DC connection mounting location - LV/MV
Load share governor
EMCP 4.4
E-Stop
Frame boxes
Annunciator modules
Load share module / auxiliary plate and auxiliary box (LV)
Fuel cooler
Controller mounting location - LV/MV
Modbus monitoring of packages
Customer interface options
EMCP 4.4 optional harness
Controller voltage and current sensing groups
Remote radiators
Generator harness
Interconnect harness
Speed adjust
Controller and MV and HV power connection locations
Raise lower switch
Explosive relief valves
Crankcase ventilation system
Mufflers
Exhaust support group
Weld flanges
Exhaust collectors/manifold
Front housing - Prime or continuous
Front housing - Standby or mission critical
Aftercooler drain
Primary fuel filter
Low voltage - 1800 and 3000 Frames - 60 Hz, 3 phase, 1800 rpm, FW, PM, No of leads=6, Pitch 0.6667
Medium voltage - 1800 and 3000 Frames - 60 Hz, 3 phase, 1800 rpm, FW, PM, No of leads=6, Pitch 0.6667
Conversion GP - Top cable entry
Low voltage - 1800 and 3000 Frames - 50 Hz, 3 phase, 1500 rpm, FW, PM, No of leads=6, Pitch 0.6667
Differential current transformers
Space heater kit
Medium voltage - 1800 and 3000 Frames - 50 Hz, 3 phase, 1500 rpm, FW, PM, No of leads=6, Pitch 0.6667
Thermostat for space heater
Generator air intake
Pyrometer and thermocouples
Drain group oil pans
Oil filters
Lube oil heater
Electric prelube pumps
Lubricating oil
IBC vibration isolators - Shipped loose
Spring type linear vibration isolators
Rubber anti-vibration mounts
Low voltage connection cable
Center post busbarss (LV)
1800 Frame generator side / rear mounted busbars (MV)
Enclosures - Control packaging (LV)
Paralleling circuit breakers
1800 Frame generators Circuit breaker
Neutral ground (LV)
Neutral ground (MV)
Cable entry options (LV)
Cable entry options (MV)
Masterpack breakers
Power connection covers (LV)
Harnesses (Breaker)
Masterpack breaker connections
Side/rear mounted busbars (LV)
IBC seismic Certification
Special test charge - Engine only
PGS Test report @ 0.8 power factor
Genset fuel consumption test
Standard genset TVA (Torsional Vibration Analysis) report
PGS Test report @ 1.0 power factor
OSCOSH1 seismic Certification
Custom generator TVA report
Generator test report
Standard engine test charge
Heavy duty battery sets with rack
Charging alternators - Dry
Air pressure regulator
Starter location covers
24 Volt power distribution box
24 Volt electric starting motor
35 Amp Battery chargers
24 Volt battery set - Dry
20 Amp Battery chargers
Jacket water heaters
50 Amp Battery chargers
Air starting motor
Jacket water heater wiring groups
Special paint colors
Control GP - air powered bar group
Barring group manual
Service tools - Engine barring group
Engine barring air powered