The Cat® ECS 300 integrates advanced site controls for both traditional and hybrid microgrid systems. The Cat ECS ensures precise management of generation assets with operational reliability and optimized cost effectiveness. The system features a user-friendly and intuitive 396 mm (15.6”) color touchscreen interface.
Application The Cat ECS 300 is used in a variety of microgrids where the Cat ECS 300 is configurable to meet applicable site-specific asset requirements.
Module Type Monitoring / control and asset optimization may be configured with up to 4 Distributed Energy Resources (DER's).
Enclosure Rating NEMA 1 wall mountable
Application The Cat ECS 300 is used in a variety of microgrids where the Cat ECS 300 is configurable to meet applicable site-specific asset requirements.
Module Type Monitoring / control and asset optimization may be configured with up to 4 Distributed Energy Resources (DER's).
Enclosure Rating NEMA 1 wall mountable
Utility parallel, import power from grid - Minimum import kW setpoint is maintained
Unplanned Islanding or Emergency standby - Closed transition (with soft unload) or Open transition
Load shed/load add - Automatic or manual load shed up to four (4) stages
Planned Islanding or Intentional islanding
Load sense/load demand - Based on asset priority or engine-hour balancing - Automatically matches on-line asset capacity to the loads
Economy mode - All Gensets and non-renewable "fuel consuming" assets OFF
Utility parallel, base load operations
Pro-active add and drop - Ability to manually bring additional gensets online in anticipation of bringing on large loads - Manually turning off gensets instead of waiting for LSLD drop when the customer knows large loads are being taken offline
Utility parallel, export power to grid - Target export setpoint is maintained
Reliability mode - At least one high priority "fuel consuming" asset ON
Scheduling - 5 schedules and 6 segments - BESS dispatch scheduling based on year, month, time, day and segment of day - 5 schedules and 6 segments -Import and export scheduling for active and reactive power based on time, day and segment of day
3 Flexible efficiency modes 1, 2 and 3 that may be set up based on asset group priorities
Grid Reactive Control mode - There are 4 available reactive power control settings- Constant VAr, Constant PF, Volt-VAr curve, Watt-VAr curve
Load smoothing mode - Non-stable load dispatch using available assets for specified durations of time
SunSpec® Compliant
NEMA Type 1
UL 508A; Note codes may not be available in all model configurations. Please consult your local Cat dealer for availability.
Telematics PLE702 (See LEHE22212) allows data logging of 300 channels for 1.5 days (requires subscription for visualization).
Best Battery Diode (BBD) for backup power supply.
Managed switch that offers configurable site communication and enhanced security provision to assure network integrity. One ethernet (4-Wire) port connection for customer networking of DER's.
3 Flexible efficiency modes 1, 2, and 3 that may be set up based on asset group priorities
Economy mode - All Gensets and non-renewable "fuel consuming" assets OFF
Pro-active add and drop - Ability to manually bring additional gensets online in anticipation of bringing on large loads - Manually turning off gensets instead of waiting for LSLD drop when the customer knows large loads are being taken offline
Load smoothing mode - Non-stable load dispatch using available assets for specified durations of time
Reliability mode - At least one high priority "fuel consuming" asset ON
Communications, power allocation test mode for site commissioning. Manually control assets and the microgrid system.
Monitoring only - Cat ECS 300 relinquish control to another site controller.
Off
Off Package HMI: The Cat ECS 300 supports a full function HMI display with the addition of an unmanaged Ethernet switch. The interactive 396 mm (15.6") color touchscreen graphical interface serves to display system alarm conditions, status indications and annunciation. (Ship loose HMI display without panel box). Contact your local Cat dealer for more information
Global team delivering advanced solutions to meet customer specifications including: Custom Cat ECS control solutions Cat ECS hardware integrated with distribution switchgear Customer specified sequence of operations Test reports per Joint Commission on Accreditation of Healthcare Organizations (JCAHO) Integrated Automatic Transfer Switch (ATS) solutions including remote start signal integrity and report generation Expanded performance capability: - Multi-bus sites - Advanced utility protections - Greater than 4-stage Load Shed - Load Add (LS/LA) functionality - Redundant PLC configurations - Weather-rated packaging (IP54 / NEMA 3R or IP52 / NEMA 12). - Larger HMIs - Up to 250 Distributed Energy Resources (DER's)
Up to 800 channels of data storage every second for 1.5 days depending on the number of devices or equipment connected to PLE702 (See LEHE22212) with options for: Cellular (part no. 550-3269) or Satellite radio + cellular (part no. 545-3987) (Requires subscription for visualization). Cellular and satellite radio module and antenna available Cat dealer installed.
Security window Service Receptacle and Light Interior 120 VAC, 5A service receptacle and light. Uninterruptable Power Supply (UPS) with lithium iron phosphate (LFP) battery, when fully charged, provides backup for a minimum of 10 minutes with a DC load of 150 watts.
The Cat ECS 300 utilizes an optional external device for utility sensing breaker control.
Utility Protection Functions - American National Standards Institute (ANSI) - Over / Under Voltage (59 / 27) - Over / Under Frequency (81O / U) - Rate of Change of Frequency (ROCOF) (81R) - Sync check (25).